Home / Calculators / Wire Size

Wire Size Calculator

Enter your load, run length and maximum % drop — this solver walks up the AWG ladder and returns the smallest conductor that passes both the ampacity floor and your voltage drop budget.

Voltage Drop
Find Wire Size
Max Length
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

How the solver works

Two independent rules govern conductor sizing. Ampacity (NEC Table 310.16) is the safety limit — the maximum continuous current a conductor can carry without overheating its insulation. Voltage drop is the performance limit — the NEC recommends no more than 3% on branch circuits and 5% total. On short runs ampacity usually governs; past roughly 100 feet, voltage drop takes over and forces conductors one or two sizes larger than ampacity alone would require.

This calculator tests each size in order against both rules, so the answer is the smallest conductor that is both safe and within your drop budget.

Solving for size
Rmax = Vd(max) × 1000 ÷ (2 × I × L)
Vd(max)budget volts = limit% × source voltage
Rmaxlargest acceptable resistance, Ω/kft
answersmallest gauge with R ≤ Rmax and Table 310.16 ampacity ≥ I

Two gates, not one: a gauge must pass the drop budget AND carry the current thermally. Physics-only calculators stop at the first gate.

Worked example — 40 A over 100 ft on 240 V (3%)

  1. Budget: 3% of 240 V = 7.20 V allowed.
  2. Rmax = 7.20 × 1000 ÷ (2 × 40 × 100) = 0.900 Ω/kft.
  3. Smallest gauge at or under 0.900 Ω/kft: 8 AWG (0.764 Ω/kft).
  4. Ampacity gate: 8 AWG carries 50 A at 75 °C ≥ 40 A load. Both gates pass.
  5. 8 AWG copper — drop 6.11 V (2.55%) at 40 A over 100 ft on 240 V.

By system voltage: 120 V · 208 V · 240 V · 277 V · 480 V · 12 V · 24 V · 48 V — and the reference hubs: wire tables, by gauge, by amperage, by distance.

Step-by-step: 50 A at 120 ft on 240 V?

Work it in three lines: budget = 3% × 240 V = 7.20 V; R(max) = 7.20 × 1000 ÷ (2 × 50 × 120) = 0.600 Ω/kft; smallest gauge under that with ampacity ≥ 50 A is 6 AWG (0.491 Ω/kft, 65 A). Actual drop: 5.89 V = 2.46%.

Frequently Asked Questions

Which governs — ampacity or voltage drop?

Whichever demands the larger conductor. Ampacity is a hard safety requirement; the 3%/5% drop figures are NEC recommendations. On long runs, voltage drop almost always forces the larger size.

What max drop should I enter?

Use 3% for branch circuits (panel to outlet) and budget the full path to 5%. Many engineers spec 2% for feeders to leave 3% for branches.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice