Ampacity Chart — NEC Table 310.16

Type your load below for the smallest qualifying size — or read the full table. Values assume ≤3 current-carrying conductors in raceway at 30 °C ambient.

SizeCu 60°CCu 75°CCu 90°CAl 60°CAl 75°CAl 90°C
14 AWG152025
12 AWG202530152025
10 AWG303540253035
8 AWG405055354045
6 AWG556575405055
4 AWG708595556575
3 AWG85100110657585
2 AWG951151307590100
1 AWG11013014585100115
1/0 AWG125150170100120135
2/0 AWG145175195115135150
3/0 AWG165200225130155175
4/0 AWG195230260150180205
250 kcmil215255290170205230
300 kcmil240285320195230260
350 kcmil260310350210250280
400 kcmil280335380225270305
500 kcmil320380430260310350

The everyday working column is 75 °C — what standard breaker and lug terminations are rated for (NEC 110.14(C)). The 90 °C column is mainly a derating start point. Small-conductor caps still apply: 15 A for 14 AWG, 20 A for 12 AWG, 30 A for 10 AWG copper (NEC 240.4(D)). For ambient or bundling corrections, use the ampacity calculator.