Home / Calculators / UK · BS 7671

UK Voltage Drop Calculator (BS 7671)

Metric cable sizes on 230 V single-phase and 400 V three-phase, checked against the BS 7671 Appendix 4 limits: 3% for lighting, 5% for other uses — including the automatic long-run allowance beyond 100 m.

What BS 7671 requires

For an installation supplied from a public LV network, BS 7671 Appendix 4 (Table 4Ab) limits voltage drop to 3% for lighting (6.9 V on 230 V) and 5% for other uses (11.5 V) between the origin and any load point. Private supplies get an extra 2-point allowance, and runs over 100 m may add 0.005%/m (capped at 0.5%). Unlike the NEC's informational notes, these are requirements verified at design and inspection.

mV/A/m and this calculator

UK design tables express cable drop as millivolts per amp per meter. This tool computes the same physics from conductor area (ρ ≈ 0.0225 Ω·mm²/m copper at operating temperature) — for 2.5 mm² that yields 18 mV/A/m, matching Table 4D2B. Three-phase values are line figures using √3.

The metric formula
Vd = 2 × I × L × ρ ÷ A
Iload current, amps
Lone-way length, meters
ρresistivity ≈ 0.0225 Ω·mm²/m copper at operating temp
Aconductor cross-section, mm²

Equivalent to the tabulated mV/A/m method: the two-core table value is exactly 2ρ/A × 1000. √3 replaces 2 for three-phase line values.

Worked example — 32 A over 30 m of 6 mm² at 230 V (5% limit)

  1. Vd = 2 × 32 × 30 × 0.0225 ÷ 6 = 7.20 V.
  2. Percent: 7.20 ÷ 230 × 100 = 3.13% — within the 5% 'other circuits' limit (App. 4 Table 4Ab).
  3. Past 100 m the calculator raises the limit automatically: +0.005%/m, capped at +0.5%.
  4. PASS at 3.13% — and the same circuit fails a 3% lighting budget. BS 7671 verdicts are circuit-type-dependent by design.

Frequently Asked Questions

Is 5% drop a legal requirement in the UK?

BS 7671 is the standard against which installations are certified — exceeding the Appendix 4 limits without justification fails design verification. In practice, yes: treat 3%/5% as binding.

What about the 0.005%/m allowance?

For installations longer than 100 m, the limit may be increased by 0.005% per meter beyond 100 m, up to an extra 0.5% — relevant for farms, long drives and outbuildings.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice