Home / Calculators / DC Wire Size Calculator

DC Wire Size Calculator

Low-voltage DC punishes thin wire: at 12 V, the 3% budget is just 0.36 volts. Enter the load and run; the solver returns the smallest real conductor that survives both the drop budget and the ampacity table — for solar, marine, vans, and automotive work.

Voltage Drop
Find Wire Size
Max Length
Presets
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

DC sizing in one idea

The same drop in volts is a much bigger percentage at low voltage — 0.9 V lost is 0.4% at 240 V but 7.5% at 12 V. That's why DC wire sizes look shockingly large to AC-trained eyes, and why doubling system voltage (12→24 V) lets the same wire carry the same power four times farther. The DC drop calculator is this tool's sibling for checking an existing wire; per-voltage sizers: 12 V · 24 V · 48 V.

Why answers here differ from physics-only calculators

Generic wire-size tools solve ρ·L/A and report a theoretical gauge — famously including sizes like "13 AWG" that don't exist at the supply house, with no check that the wire can carry the current thermally. This calculator returns only real, purchasable conductors, enforces the NEC ampacity floor for the load, applies the drop budget, and shows the verdict — wire you can actually buy and legally install. Every result comes with the fan chart, upgrade economics, and a PDF report.

Solving for size
Rmax = Vd(max) × 1000 ÷ (2 × I × L)
Vd(max)budget volts = limit% × source voltage
Rmaxlargest acceptable resistance, Ω/kft
answersmallest gauge with R ≤ Rmax and Table 310.16 ampacity ≥ I

Two gates, not one: a gauge must pass the drop budget AND carry the current thermally. Physics-only calculators stop at the first gate.

Worked example — 30 A over 20 ft on 12 V (3%)

  1. Budget: 3% of 12 V = 0.36 V allowed.
  2. Rmax = 0.36 × 1000 ÷ (2 × 30 × 20) = 0.300 Ω/kft.
  3. Smallest gauge at or under 0.300 Ω/kft: 3 AWG (0.245 Ω/kft).
  4. Ampacity gate: 3 AWG carries 100 A at 75 °C ≥ 30 A load. Both gates pass.
  5. 3 AWG copper — drop 0.29 V (2.45%) at 30 A over 20 ft on 12 V.

For contrast, the pure area formula gives A = 2ρLI/V = 2 × 0.0225 × 6.1 × 30 ÷ 0.36 ≈ 22.9 mm² — a size that doesn't exist at any supply house. Real conductors, real gates.

Step-by-step: what size wire for 25 A at 30 ft on 12 V?

Work it in three lines: budget = 3% × 12 V = 0.36 V; R(max) = 0.36 × 1000 ÷ (2 × 25 × 30) = 0.240 Ω/kft; smallest gauge under that with ampacity ≥ 25 A is 2 AWG (0.194 Ω/kft, 115 A). Actual drop: 0.29 V = 2.42%.

Frequently Asked Questions

What size wire for 30 amps DC at 25 feet?

On 12 V at a 3% budget: 4 AWG copper. The same load on 24 V needs only 8 AWG, and on 48 V, 12 AWG (ampacity-limited) — the calculator above shows all three in two clicks.

Do I use 3% or 10% for DC?

3% for voltage-sensitive loads (fridges, electronics, charge circuits) per common practice and ABYC guidance for critical circuits; up to 10% is tolerated for non-critical loads like resistive heaters and some lighting.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice