Home / Reference / Standards Hub — How the World Sizes Wire

Standards Hub — How the World Sizes Wire

Same physics, six rulebooks. The table compares units, method, limits and — the part that surprises people — whether the limit is a recommendation or law. *NEC figures become binding under energy codes, fire pump rules and adopting specs.

StandardUnitsMethodLimitStatusSource
NEC (US)AWG · feetCh.9 Tbl.8 R / K-factor3% / 5%Recommended*NFPA 70
CEC (Canada)AWG · feetSame physics as NEC3% / 5%MandatoryCSA C22.1, Rule 8-102
BS 7671 (UK)mm² · metersmV/A/m, Appendix 43% lighting / 5% otherVerified at certificationBS 7671 App. 4
AS/NZS (AU/NZ)mm² · meters3Ø mV/A/m (×1.155 for 1Ø)5% totalMandatoryAS/NZS 3000 + 3008.1
IS 732 (India)sq mm · metersIEC method4% default; 3%/5% commonPer specIS 732:2019 / IEC
IEC 60364mm² · metersρ/A metric4% defaultInformative60364-5-52 Annex G

One engine, every standard

Every method on this page reduces to Vd = (factor) × I × L × R, differing only in units, tabulation style and the percentage you're held to. This site runs the AWG engine for NEC/CEC work and the metric engine for the IEC family — pick your standard above and the right calculator, limits and conventions are preset.

Working across borders? The AWG ⇄ mm² converter translates the hardware, and the comparison rows above translate the law.