Home / Calculators / 24V Wire Size Calculator

24V Wire Size Calculator

Enter the load and one-way distance; get the smallest real conductor that passes both the drop budget and the ampacity check on a 24 V system.

Voltage Drop
Find Wire Size
Max Length
Presets
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

24 V is the sweet spot for serious trolling motors and mid-size off-grid systems: same power as 12 V at half the current, which means one-quarter of the copper for the same percentage drop.

Why answers here differ from physics-only calculators

Generic wire-size tools solve ρ·L/A and report a theoretical gauge — famously including sizes like "13 AWG" that don't exist at the supply house, with no check that the wire can carry the current thermally. This calculator returns only real, purchasable conductors, enforces the NEC ampacity floor for the load, applies the drop budget, and shows the verdict — wire you can actually buy and legally install. Every result comes with the fan chart, upgrade economics, and a PDF report.

Siblings: DC wire size hub · 24V voltage drop (check an existing wire) · metric sizes.

Solving for size
Rmax = Vd(max) × 1000 ÷ (2 × I × L)
Vd(max)budget volts = limit% × source voltage
Rmaxlargest acceptable resistance, Ω/kft
answersmallest gauge with R ≤ Rmax and Table 310.16 ampacity ≥ I

Two gates, not one: a gauge must pass the drop budget AND carry the current thermally. Physics-only calculators stop at the first gate.

Worked example — 30 A over 30 ft on 24 V (3%)

  1. Budget: 3% of 24 V = 0.72 V allowed.
  2. Rmax = 0.72 × 1000 ÷ (2 × 30 × 30) = 0.400 Ω/kft.
  3. Smallest gauge at or under 0.400 Ω/kft: 4 AWG (0.308 Ω/kft).
  4. Ampacity gate: 4 AWG carries 85 A at 75 °C ≥ 30 A load. Both gates pass.
  5. 4 AWG copper — drop 0.55 V (2.31%) at 30 A over 30 ft on 24 V. A typical solar array feed.

Step-by-step: 48 A at 25 ft on 24 V?

Work it in three lines: budget = 3% × 24 V = 0.72 V; R(max) = 0.72 × 1000 ÷ (2 × 48 × 25) = 0.300 Ω/kft; smallest gauge under that with ampacity ≥ 48 A is 3 AWG (0.245 Ω/kft, 100 A). Actual drop: 0.59 V = 2.45%.

Frequently Asked Questions

What size wire for a 24V trolling motor at 25 ft?

A typical 48 A motor needs 3 AWG copper at a strict 3% budget (6 AWG lands at 4.9% — the common 5%-class pick), versus 1/0 if it were a 12 V system. That difference is the entire argument for 24 V.

Why does 24V need so much less copper than 12V?

Half the current for the same watts AND double the voltage base for the percentage: the two effects multiply to a 4× advantage in allowable resistance.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice