Home / Calculators / 12V Wire Size Calculator

12V Wire Size Calculator

Enter the load and one-way distance; get the smallest real conductor that passes both the drop budget and the ampacity check on a 12 V system.

Voltage Drop
Find Wire Size
Max Length
Presets
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

12 V is the harshest sizing environment in common use — a 0.36 V budget at 3% — and the biggest audience: vans, boats, RVs, automotive and small solar. Rules of thumb that work at 120 V fail by a factor of ten here.

Why answers here differ from physics-only calculators

Generic wire-size tools solve ρ·L/A and report a theoretical gauge — famously including sizes like "13 AWG" that don't exist at the supply house, with no check that the wire can carry the current thermally. This calculator returns only real, purchasable conductors, enforces the NEC ampacity floor for the load, applies the drop budget, and shows the verdict — wire you can actually buy and legally install. Every result comes with the fan chart, upgrade economics, and a PDF report.

Siblings: DC wire size hub · 12V voltage drop (check an existing wire) · metric sizes.

Solving for size
Rmax = Vd(max) × 1000 ÷ (2 × I × L)
Vd(max)budget volts = limit% × source voltage
Rmaxlargest acceptable resistance, Ω/kft
answersmallest gauge with R ≤ Rmax and Table 310.16 ampacity ≥ I

Two gates, not one: a gauge must pass the drop budget AND carry the current thermally. Physics-only calculators stop at the first gate.

Worked example — 8 A over 18 ft on 12 V (3%)

  1. Budget: 3% of 12 V = 0.36 V allowed.
  2. Rmax = 0.36 × 1000 ÷ (2 × 8 × 18) = 1.250 Ω/kft.
  3. Smallest gauge at or under 1.250 Ω/kft: 10 AWG (1.21 Ω/kft).
  4. Ampacity gate: 10 AWG carries 35 A at 75 °C ≥ 8 A load. Both gates pass.
  5. 10 AWG copper — drop 0.35 V (2.90%) at 8 A over 18 ft on 12 V. The compressor-fridge case that 16 AWG 'rules of thumb' get wrong.

Step-by-step: 50 A trolling motor at 20 ft, strict 3%?

Work it in three lines: budget = 3% × 12 V = 0.36 V; R(max) = 0.36 × 1000 ÷ (2 × 50 × 20) = 0.180 Ω/kft; smallest gauge under that with ampacity ≥ 50 A is 1 AWG (0.154 Ω/kft, 130 A). Actual drop: 0.31 V = 2.57%.

Frequently Asked Questions

What size wire for a 12V trolling motor?

At a strict 3% budget, a 50 A motor at 20 ft one-way needs 1 AWG copper — 4 AWG lands at 5.1%, acceptable only as a non-critical 5%-class choice. At 30 ft, 3% demands 2/0. Undersized cable is the #1 cause of 'weak' trolling motors.

Can I use the 10% rule for 12V?

Only for non-critical resistive loads. Compressor fridges cut out near 11.5 V, so their circuits deserve the 3% treatment.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice