Home / Calculators / AS/NZS 3008

AS/NZS 3008 Method (Australia / NZ)

The Australasian approach: a hard 5% cap from the point of supply to any point of the installation (AS/NZS 3000), with cable data tabulated in AS/NZS 3008.1 as three-phase mV/A/m — and the famous trap that single-phase circuits must multiply the tabulated value by 1.155 — handled automatically below.

Budgeting the 5%

The cap covers the whole path, so designers allocate it across stages — a common pattern is roughly 1.5% consumer mains, 1.5% submains, 2% final subcircuits, but any split that sums within 5% complies. Model a real chain stage-by-stage with the multi-segment calculator.

CableΩ/km (per cond.)3Ø mV/A/mRating A
1.5 mm²15.00026.020
2.5 mm²9.00015.627
4 mm²5.6259.737
6 mm²3.7506.547
10 mm²2.2503.964
16 mm²1.4062.485
25 mm²0.9001.6112
35 mm²0.6431.1138

The tabulated three-phase value equals √3 × ρ/A × 1000; multiply by 1.155 (2/√3) for single-phase — this calculator handles that automatically via the system selector. Full context on the Australia/NZ calculator page.

Frequently Asked Questions

Is 5% a recommendation like the NEC's?

No — AS/NZS 3000 makes it a requirement of the Wiring Rules, checked at inspection. The NEC's equivalent figures are informational notes unless adopted elsewhere.

Why do AS/NZS tables quote three-phase values?

Convention: most distribution design is three-phase, so 3008.1 tabulates the line-to-line figure and lets single-phase designers apply the 1.155 factor.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice