Wire Size for 200 Amps at 100 Feet

For a 200 A feeder at 100 feet (one-way), you need 3/0 AWG copper or 250 kcmil aluminum at 240 V and a 3% drop. Feeders are usually budgeted tighter — at 2% (leaving 3% for branch circuits): 3/0 AWG copper / 250 kcmil aluminum.

Voltage Drop
Find Wire Size
Max Length
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

At feeder budgets — 240 V

Drop budgetCopperAluminum
2% (feeder best practice)3/0 AWG250 kcmil
3% (NEC branch note)3/0 AWG250 kcmil
5% (NEC total)3/0 AWG250 kcmil

A 200 A run at this distance is service-class feeder territory: aluminum (SER, mobile-home feeder, or XHHW in conduit) is the standard economic choice at these sizes with AL-rated, torqued terminations. Where the table says parallel sets, NEC 310.10(G) applies — 1/0 minimum per conductor, matched lengths. Budget 2% here so downstream branch circuits keep 3% of the 5% total; model the whole chain in the multi-segment calculator.

Frequently Asked Questions

Copper or aluminum for a 200 A feeder?

Aluminum, almost always — at 200 A sizes the price gap is large and modern AA-8000 feeder cable is fully standard. The table shows both at every budget.

Why does my electrician quote a bigger wire than the 3% column?

Feeder practice reserves drop budget for the branches beyond the subpanel — the 2% column is the professional default, and some bids also size for future load growth.