Home / Calculators / 20 A @ 300 ft

Wire Size for 20 Amps at 300 Feet

For 20 amps at 300 feet (one-way), you need 6 AWG copper at 240 V or 3 AWG copper at 120 V to stay within the NEC-recommended 3% voltage drop. In aluminum at 240 V: 4 AWG.

Voltage Drop
Find Wire Size
Max Length
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

At both NEC budgets

Drop budget120 V copper240 V copper240 V aluminum
3% (NEC branch)3 AWG6 AWG4 AWG
5% (NEC total)6 AWG8 AWG6 AWG

Distance is one-way; the round trip is built into the formula. The 3% figure is the NEC branch-circuit recommendation — use it unless the load is tolerant and the path already meets the 5% total budget. Verify the final pick against breaker size and termination ratings.

Frequently Asked Questions

Why does 120 V need bigger wire than 240 V for the same 20 A?

The absolute volts lost are identical, but they are a larger percentage of 120 V — so the budget runs out twice as fast. Running the same power at 240 V also halves the current, compounding the advantage.

Does the 300 ft figure mean total wire purchased?

No — 300 ft is the one-way route distance. You will buy roughly twice that in conductor for a single-phase circuit, which the calculation already accounts for.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice