Home / Calculators / 100 A @ 300 ft

Wire Size for 100 Amps at 300 Feet

For a 100 A feeder at 300 feet (one-way), you need 2/0 AWG copper or 4/0 AWG aluminum at 240 V and a 3% drop. Feeders are usually budgeted tighter — at 2% (leaving 3% for branch circuits): 3/0 AWG copper / 300 kcmil aluminum.

Voltage Drop
Find Wire Size
Max Length
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

At feeder budgets — 240 V

Drop budgetCopperAluminum
2% (feeder best practice)3/0 AWG300 kcmil
3% (NEC branch note)2/0 AWG4/0 AWG
5% (NEC total)2 AWG2/0 AWG

A 100 A run at this distance is subpanel feeder territory: aluminum (SER, mobile-home feeder, or XHHW in conduit) is the standard economic choice at these sizes with AL-rated, torqued terminations. Where the table says parallel sets, NEC 310.10(G) applies — 1/0 minimum per conductor, matched lengths. Budget 2% here so downstream branch circuits keep 3% of the 5% total; model the whole chain in the multi-segment calculator.

Frequently Asked Questions

Copper or aluminum for a 100 A feeder?

Aluminum, almost always — at 100 A sizes the price gap is large and modern AA-8000 feeder cable is fully standard. The table shows both at every budget.

Why does my electrician quote a bigger wire than the 3% column?

Feeder practice reserves drop budget for the branches beyond the subpanel — the 2% column is the professional default, and some bids also size for future load growth.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice