Home / Calculators / 70 mm²

70 mm² Cable — Voltage Drop & Max Length

70 mm² copper is rated about 213 A installed per Method C (clipped direct, 70 °C thermoplastic) and drops 0.6 mV/A/m (single-phase figure, matching BS 7671 Appendix 4 within rounding). The chart shows how far it runs before the drop exceeds the limits.

Max one-way run — 70 mm² copper

Load230 V @ 3%230 V @ 5%400 V 3Ø @ 5%
6 A1789 m2981 m5987 m
10 A1073 m1789 m3592 m
16 A671 m1118 m2245 m
20 A537 m894 m1796 m
32 A335 m559 m1123 m
40 A268 m447 m898 m
63 A170 m284 m570 m

Computed with ρ ≈ 0.0225 Ω·mm²/m (copper at operating temperature), matching BS 7671 Appendix 4 mV/A/m values within rounding. Grouping, insulation type and installation method change the amp rating — treat 213 A as the Method C reference figure.

Frequently Asked Questions

What is 70 mm² in AWG?

The nearest equal-or-larger AWG size is 3/0 AWG — see the gauge converter for exact areas.

How many amps can 70 mm² cable take?

About 213 A for copper clipped direct (Method C). Enclosed in conduit in insulation it derates substantially — always check the installation method column in BS 7671 Appendix 4.