16 mm² Cable — Voltage Drop & Max Length

16 mm² copper is rated about 85 A installed per Method C (clipped direct, 70 °C thermoplastic) and drops 2.8 mV/A/m (single-phase figure, matching BS 7671 Appendix 4 within rounding). The chart shows how far it runs before the drop exceeds the limits.

Max one-way run — 16 mm² copper

Load230 V @ 3%230 V @ 5%400 V 3Ø @ 5%
6 A409 m681 m1369 m
10 A245 m409 m821 m
16 A153 m256 m513 m
20 A123 m204 m411 m
32 A77 m128 m257 m
40 A61 m102 m205 m
63 A39 m65 m130 m

Computed with ρ ≈ 0.0225 Ω·mm²/m (copper at operating temperature), matching BS 7671 Appendix 4 mV/A/m values within rounding. Grouping, insulation type and installation method change the amp rating — treat 85 A as the Method C reference figure.

Frequently Asked Questions

What is 16 mm² in AWG?

The nearest equal-or-larger AWG size is 4 AWG — see the gauge converter for exact areas.

How many amps can 16 mm² cable take?

About 85 A for copper clipped direct (Method C). Enclosed in conduit in insulation it derates substantially — always check the installation method column in BS 7671 Appendix 4.