120 mm² Cable — Voltage Drop & Max Length

120 mm² copper is rated about 299 A installed per Method C (clipped direct, 70 °C thermoplastic) and drops 0.4 mV/A/m (single-phase figure, matching BS 7671 Appendix 4 within rounding). The chart shows how far it runs before the drop exceeds the limits.

Max one-way run — 120 mm² copper

Load230 V @ 3%230 V @ 5%400 V 3Ø @ 5%
6 A3067 m5111 m10264 m
10 A1840 m3067 m6158 m
16 A1150 m1917 m3849 m
20 A920 m1533 m3079 m
32 A575 m958 m1925 m
40 A460 m767 m1540 m
63 A292 m487 m978 m

Computed with ρ ≈ 0.0225 Ω·mm²/m (copper at operating temperature), matching BS 7671 Appendix 4 mV/A/m values within rounding. Grouping, insulation type and installation method change the amp rating — treat 299 A as the Method C reference figure.

Frequently Asked Questions

What is 120 mm² in AWG?

The nearest equal-or-larger AWG size is 250 kcmil — see the gauge converter for exact areas.

How many amps can 120 mm² cable take?

About 299 A for copper clipped direct (Method C). Enclosed in conduit in insulation it derates substantially — always check the installation method column in BS 7671 Appendix 4.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice