Home / Calculators / 10 mm²

10 mm² Cable — Voltage Drop & Max Length

10 mm² copper is rated about 64 A installed per Method C (clipped direct, 70 °C thermoplastic) and drops 4.5 mV/A/m (single-phase figure, matching BS 7671 Appendix 4 within rounding). The chart shows how far it runs before the drop exceeds the limits.

Max one-way run — 10 mm² copper

Load230 V @ 3%230 V @ 5%400 V 3Ø @ 5%
6 A256 m426 m855 m
10 A153 m256 m513 m
16 A96 m160 m321 m
20 A77 m128 m257 m
32 A48 m80 m160 m
40 A38 m64 m128 m
63 A24 m41 m81 m

Computed with ρ ≈ 0.0225 Ω·mm²/m (copper at operating temperature), matching BS 7671 Appendix 4 mV/A/m values within rounding. Grouping, insulation type and installation method change the amp rating — treat 64 A as the Method C reference figure.

Frequently Asked Questions

What is 10 mm² in AWG?

The nearest equal-or-larger AWG size is 6 AWG — see the gauge converter for exact areas.

How many amps can 10 mm² cable take?

About 64 A for copper clipped direct (Method C). Enclosed in conduit in insulation it derates substantially — always check the installation method column in BS 7671 Appendix 4.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice