1.5 mm² Cable — Voltage Drop & Max Length

1.5 mm² copper is rated about 20 A installed per Method C (clipped direct, 70 °C thermoplastic) and drops 30.0 mV/A/m (single-phase figure, matching BS 7671 Appendix 4 within rounding). The chart shows how far it runs before the drop exceeds the limits.

Max one-way run — 1.5 mm² copper

Load230 V @ 3%230 V @ 5%400 V 3Ø @ 5%
6 A38 m64 m128 m
10 A23 m38 m77 m
16 A14 m24 m48 m
20 A12 m19 m38 m

Computed with ρ ≈ 0.0225 Ω·mm²/m (copper at operating temperature), matching BS 7671 Appendix 4 mV/A/m values within rounding. Grouping, insulation type and installation method change the amp rating — treat 20 A as the Method C reference figure.

Frequently Asked Questions

What is 1.5 mm² in AWG?

The nearest equal-or-larger AWG size is 14 AWG — see the gauge converter for exact areas.

How many amps can 1.5 mm² cable take?

About 20 A for copper clipped direct (Method C). Enclosed in conduit in insulation it derates substantially — always check the installation method column in BS 7671 Appendix 4.