Home / Calculators / 70 Amp

What Size Wire for 70 Amps?

By ampacity alone, a 70 A circuit needs 4 AWG copper (or 3 AWG aluminum) at the 75 °C column. But past a certain distance, voltage drop — not ampacity — picks the size. The chart below shows the real answer.

Voltage Drop
Find Wire Size
Max Length
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

Minimum size by distance — 3% drop

One-way distance120 V copper240 V copper240 V aluminum
25 ft4 AWG4 AWG3 AWG
50 ft4 AWG4 AWG3 AWG
75 ft4 AWG4 AWG3 AWG
100 ft3 AWG4 AWG3 AWG
150 ft1 AWG4 AWG2 AWG
200 ft1/0 AWG3 AWG1 AWG
300 ft3/0 AWG1 AWG2/0 AWG
500 ft300 kcmil2/0 AWG4/0 AWG

Short runs are governed by ampacity; long runs by drop. For this load the crossover happens where the table first steps above 4 AWG. For a 5% total budget the distances stretch 1.67×. Continuous loads (3+ hours) must also be breakered at 125% — size the overcurrent device accordingly.

Frequently Asked Questions

Can I use 4 AWG for 70 amps at any distance?

Only where the drop stays acceptable. 4 AWG copper handles 70 A thermally, but on a long run the voltage drop will exceed 3% — check the distance chart or the calculator above.

What breaker goes with a 70 A circuit?

The conductor must be protected at or below its ampacity (per NEC 240.4); continuous loads are calculated at 125%. Breaker sizing is a separate check from voltage drop.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice