Home / Calculators / 30 Amp

What Size Wire for 30 Amps?

By ampacity alone, a 30 A circuit needs 10 AWG copper (or 10 AWG aluminum) at the 75 °C column. But past a certain distance, voltage drop — not ampacity — picks the size. The chart below shows the real answer.

Voltage Drop
Find Wire Size
Max Length
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

Minimum size by distance — 3% drop

One-way distance120 V copper240 V copper240 V aluminum
25 ft10 AWG10 AWG10 AWG
50 ft8 AWG10 AWG10 AWG
75 ft8 AWG10 AWG8 AWG
100 ft6 AWG8 AWG6 AWG
150 ft4 AWG8 AWG4 AWG
200 ft3 AWG6 AWG4 AWG
300 ft2 AWG4 AWG2 AWG
500 ft2/0 AWG2 AWG1/0 AWG

Short runs are governed by ampacity; long runs by drop. For this load the crossover happens where the table first steps above 10 AWG. For a 5% total budget the distances stretch 1.67×. Continuous loads (3+ hours) must also be breakered at 125% — size the overcurrent device accordingly.

Frequently Asked Questions

Can I use 10 AWG for 30 amps at any distance?

Only where the drop stays acceptable. 10 AWG copper handles 30 A thermally, but on a long run the voltage drop will exceed 3% — check the distance chart or the calculator above.

What breaker goes with a 30 A circuit?

The conductor must be protected at or below its ampacity (with the small-conductor caps of NEC 240.4(D) for 14–10 AWG); continuous loads are calculated at 125%. Breaker sizing is a separate check from voltage drop.

Built & maintained by Murugan Vellaichamy · Every calculation verified against NEC Chapter 9 Table 8 & Table 310.16 published values · Informational reference — not engineering advice