What Size Wire for 200 Amps?

By ampacity alone, a 200 A circuit needs 3/0 AWG copper (or 250 kcmil aluminum) at the 75 °C column. But past a certain distance, voltage drop — not ampacity — picks the size. The chart below shows the real answer.

Voltage Drop
Find Wire Size
Max Length
Advanced — units, power factor, parallel sets, energy cost
PASS
Voltage Drop
Percent Drop
Voltage at Load
Power Lost
Wire Resistance
Ampacity 75°C
0%3% branch5% total8%+

Minimum size by distance — 3% drop

One-way distance120 V copper240 V copper240 V aluminum
25 ft3/0 AWG3/0 AWG250 kcmil
50 ft3/0 AWG3/0 AWG250 kcmil
75 ft3/0 AWG3/0 AWG250 kcmil
100 ft3/0 AWG3/0 AWG250 kcmil
150 ft250 kcmil3/0 AWG250 kcmil
200 ft300 kcmil3/0 AWG250 kcmil
300 ft500 kcmil250 kcmil400 kcmil
500 ft>500 kcmil400 kcmil>500 kcmil

Short runs are governed by ampacity; long runs by drop. For this load the crossover happens where the table first steps above 3/0 AWG. For a 5% total budget the distances stretch 1.67×. Continuous loads (3+ hours) must also be breakered at 125% — size the overcurrent device accordingly.

Frequently Asked Questions

Can I use 3/0 AWG for 200 amps at any distance?

Only where the drop stays acceptable. 3/0 AWG copper handles 200 A thermally, but on a long run the voltage drop will exceed 3% — check the distance chart or the calculator above.

What breaker goes with a 200 A circuit?

The conductor must be protected at or below its ampacity (per NEC 240.4); continuous loads are calculated at 125%. Breaker sizing is a separate check from voltage drop.